This article will explore the most common core styles used in distribution transformers. There are two main types we’ll focus on–laminated, and wrapped (distributed gap) cores. To begin with, we’ll take a look at the basic function of the core and its associated parts.
Click here to get more.
A transformer core is a structure of thin laminated sheets of ferrous metal (most commonly silicon steel) stacked together, that the primary and secondary windings of the transformer are wrapped around.
A transformer core is composed of limbs and yokes that are joined together to form a single structure around which the coils are placed. The manner in which the respective yoke and limbs join together will depend on the type and design of the core.
In the above example, the limbs of the core are the vertical sections which the coils are formed around. The limbs can also be located on the exterior of the outermost coils in the case of some core designs. The limbs on a transformer core can also be referred to as legs.
The yoke is the horizontal section of the core which joins the limbs together. The yoke and limbs form a pathway for magnetic flux to flow freely.
The transformer core ensures efficient magnetic coupling between the windings, facilitating the transfer of electrical energy from the primary side to the secondary side.
When you have two coils of wire side by side and you pass an electric current through one of them, an electromagnetic field is induced in the second coil, which can be represented by several symmetrical lines with direction emanating from north to south pole–called lines of flux. With the coils alone, the path of the flux will be unfocused and the density of the flux will be low. As the magnetic field activates, the transformer core expands and contracts, creating the typical transformer hum.
Adding an iron core inside the coils focuses and magnifies the flux to make for a more efficient transfer of energy from primary to secondary. This is because the permeability of iron is much higher than that of air. If we think of electromagnetic flux like a bunch of cars going from one place to another, wrapping a coil around an iron core is like replacing a winding dirt road with an interstate highway. It’s much more efficient.
The densely packed laminated sheets that cores are constructed from, reduce overheating and circulating currents in the core. This lowers the transformers energy loss. Removing any air gaps between the laminations will result in a higher efficiency as well. A core design with large gaps between laminated sheets will yield higher no load or iron losses and a lower efficiency.
The earliest transformer cores utilized solid iron, however, methods developed over the years to refine raw iron ore into more permeable materials such as silicon steel, which is used today for transformer core designs due to its higher permeability. Also, the use of many densely packed laminated sheets reduces issues of circulating currents and overheating caused by solid iron core designs. Further increases in core design are made through cold rolling, annealing, and using grain oriented steel.
Silicon steel is a softer metal. Cold rolling silicon steel will increase its strength–making it more durable when assembling the core and coils together.
The annealing process involves heating the core steel up to a high temperature to remove impurities. This process will increase the softness and ductility of the metal.
Silicon steel already has a very high permeability, but this can be increased even further by orienting the grain of the steel in the same direction. Grain oriented steel can increase flux density by 30%.
Another important point to consider is how the core is formed around the windings. The core and coils can be configured with either a shell type or core type design.
With a shell-type configuration, the core surrounds the windings. This creates a closed pathway surrounding the windings for magnetic flux to flow. This design also typically yields less energy loss than a core type design. A shell type design is the classification for most distribution class padmounts and substations with a wrapped 5-legged core.
A core type design is where the windings surround the core steel. In this design, there is no return path (or closed loop) for the magnetic flux around the coils. This design typically yields more energy losses, and it requires more copper or aluminum winding material than a shell-type configuration.
Three limb (or leg) cores are frequently used for distribution class dry-type transformers–both low and medium voltage types. The three limb stacked core design is also used for larger oil-filled power class transformers. It is less common to see a three limb core used for oil-filled distribution transformers.
For more information, please visit Haoshuo.
Due to the absence of an outer limb(s), the three legged core alone is not suitable for wye-wye transformer configurations. As the picture below shows, there is no return path for the zero sequence flux which is present in wye-wye transformer designs. The zero sequence current, with no adequate return path, will attempt to create an alternate path, either using air gaps or the transformer tank itself, which can eventually lead to overheating and possibly transformer failure.
(Learn how transformers deal with heat through their cooling class)
One way this problem is solved is by adding a buried delta tertiary winding which provides a place for the flux to circulate freely. Other solutions for wye-wye transformers would include utilizing a 4-limb or 5-limb core as described below.
Rather than employ a buried delta tertiary winding, a four limb core design provides one outer limb for return flux. This type of core design is very similar to a five limb design as well in its functionality, which helps to reduce overheating and additional transformer noise.
Five-legged wrapped core designs are the standard for all distribution transformer applications today (regardless of whether or not the unit is wye-wye). Since the cross sectional area of the three inner limbs surrounded by the coils is double the size of the three limb design, the cross sectional area of the yoke and outer limbs can be half that of the inner limbs. This helps conserve material and reduce production costs as well.
There are two main types of transformer cores, distributed gap and laminated core (sometimes referred to as stacked)
Commonly referred to as a wrapped core, this core design is used in 3-ph and 1-ph distribution transformers. Distributed gap cores utilize a simple core clamp design which leads to faster assembly times and lower manufacturing costs. Another advantage of the distributed gap design is that there is only one cut per layer of laminated sheet. This type of core configuration is also referred to as a shell since the windings are surrounded by the core. As we mentioned earlier, this shell type design typically yields lower transformer losses. It’s efficient and lower cost design makes it the ideal choice for distribution transformers.
To form these distributed gap cores, multiple layers of laminated metal are placed inside a compression machine that forms their general shape.
(The picture below shows a distributed gap design. Each laminated sheet is formed around another and fit together with a step-lap joint)
Also referred to as a stacked core or E core, this type of core design employs a step-lap mitred configuration for the core sections. The laminations for each limb are grouped together in groups of 5 - 7 sheets–these groups are referred to as books. These sections of core steel are mitre cut and fit together as shown below.
(the photo above shows several books step-lapped and stacked together to form a point where an outer limb and the yoke are joined together by a mitre cut).
(The figure above shows the mitre cuts in the core which join the yoke and limbs together)
Although less common, amorphous cores are worth mentioning here–especially with growing demands for higher efficiency transformers (Check out our article on Transformer DOE Efficiency Standards). Known as tape wound cores, these core designs employ densely packed ribbon-like strips of highly permeable metallic-glass material. This makes for a more brittle core construction, but a higher efficiency. To keep the sheets together, amorphous cores are often encased in epoxy, or taped together. The no load losses are lower and core saturation levels are higher than conventional core designs. Amorphous cores are more costly than conventional cores, but their higher efficiency makes them a popular choice for special, custom applications.
There will be some loss of energy with any core configuration, but the better the core design, the less the no load losses. A well built transformer core help offset operating costs of the transformer and extend its lifespan.
Core designs have come a long way since the early days of transformer manufacturing, but the basic principles remain the same. Fill out the form below if you have any questions about transformer core design or are looking for a quote on a specific transformer.
GEORG and WEG Transformers USA are very proud to announce the inauguration of the first US installed GEORG TBA 400 robotline at WEG Transformers USA facility in Washington, MO on April 15th, .
The ribbon cutting ceremony was attended by representatives of both companies including our CEO Mark Georg and WEG Executive Management and Board Members from US, Mexico and Brazil.
We are extremely proud and honored having successfully realized this project together with WEG ahead of the originally considered timeframe.
This is another major milestone in the continuation of the unique relationship between our two companies which is based on trust, partnership and common values.
If you want to learn more, please visit our website transformer core making machine.