With the move from analog to digital, new demands are placed on the battery. Unlike analog portable devices that draw a steady current, the digital equipment loads the battery with short, heavy current spikes.
If you want to learn more, please visit our website.
One of the urgent requirements of a battery for digital applications is low internal resistance. Measured in milliohms, the internal resistance is the gatekeeper that, to a large extent, determines the runtime. The lower the resistance, the less restriction the battery encounters in delivering the needed power spikes. A high mW reading can trigger an early 'low battery' indication on a seemingly good battery because the available energy cannot be delivered in the required manner and remains in the battery
Figure 1 demonstrates the voltage signature and corresponding runtime of a battery with low, medium and high internal resistance when connected to a digital load. Similar to a soft ball that easily deforms when squeezed, the voltage of a battery with high internal resistance modulates the supply voltage and leaves dips, reflecting the load pulses. These pulses push the voltage towards the end-of-discharge line, resulting in a premature cut-off. As seen in the chart, the internal resistance governs much of the runtime.
As part of ongoing research to measure the runtime of batteries with various internal resistance levels, Cadex Electronics examined several cell batteries that had been in service for a while. All batteries were similar in size and generated good capacity readings when checked with a battery analyzer under a steady discharge load. The nickel-cadmium pack produced a capacity of 113%, nickel-metal-hydride checked in at 107% and the lithium-ion provided 94%. The internal resistance varied widely and measured a low 155 mOhm for nickel-cadmium, a high 778 mOhm for nickel-metal-hydride and a moderate 320 mOhm for lithium-ion. These internal resistance readings are typical of aging batteries with these chemistries.
Let's now check how the test batteries perform on a cell . The maximum pulse current of a GSM (Global System for Mobile Communications) cell phones is 2.5 amperes. This represents a large current from a relatively small battery of about 800 milliampere (mAh) hours. A current pulse of 2.4 amperes from an 800 mAh battery, for example, correspond to a C-rate of 3C. This is three times the current rating of the battery. Such high current pulses can only be delivered if the internal battery resistance is low.
Figures 2, 3 and 4 reveal the talk time of the three batteries under a simulated GSM current of 1C, 2C and 3C. One can see a direct relationship between the battery's internal resistance and the talk time. nickel-cadmium performed best under the circumstances and provided a talk time of 120 minutes at a 3C discharge (orange line). nickel-metal-hydride performed only at 1C (blue line) and failed at 3C. lithium-ion allowed a moderate 50 minutes talk time at 3C.
The internal resistance varies with the state-of-charge of the battery. The largest changes are noticeable on nickel-based batteries. In Figure 5, we observe the internal resistance of nickel-metal-hydride when empty, during charge, at full charge and after a 4-hour rest period.
The resistance levels are highest at low state-of-charge and immediately after charging. Contrary to popular belief, the best battery performance is not achieved immediately after a full charge but following a rest period of a few hours. During discharge, the internal battery resistance decreases, reaches the lowest point at half charge and starts creeping up again (dotted line).
Abstract
In order to remain reliable, stationary batteries require maintenance and care over their service life. A large number of tests have been performed and described in order to determine the condition of the battery. Capacity tests are used to reliably determine battery capacity. The results of capacity tests are then used to evaluate whether the battery can continue in service or needs to be replaced. Many batteries do not receive regular capacity testing due to several myths and misunderstandings, also the measurement of battery resistance is becoming a popular alternative test method. Both tests are useful in detecting deteriorated cells, however there are some initiatives to replace capacity testing with internal resistance testing. This paper shows some field experiences with internal resistance tests and capacity testing. In addition, it provides a comparison between these two tests. The conclusion discusses some merits and short comings of each test.
Battery internal resistance has been a huge topic among battery users and battery manufacturers. In recent years there has been considerable activity and comments in the use of internal resistance measurements for the assessment of the state of health of batteries.
The main reason for this is that many battery users perceive capacity testing as both complicated and expensive. The goal is to find an alternative test method in order to replace battery capacity testing.
The available techniques are AC impedance and conductance methods as well as DC loading, which measures some form of a cell’s internal resistance.
As a battery cell ages and loses capacity, its vital components (plates, grids, and connection straps) undergo unavoidable degradation. Internal resistance measurements are intended to measure this change in resistance. Measured increase in resistance indicates likely degradation and a corresponding loss of capacity.
Table 1 shows the effect of several factors on internal resistance and capacity. Factor Internal cell resistance Effect on capacity Comments Grid corrosion Increase Decrease Natural aging process. Grid swelling and expansion Increase Decrease Loss of contact between active material and grid. Loss of active material Increase Decrease Active material sheds from plates, forming sediment. Discharge Increase Decrease Either self-discharge or load discharge. Sulfation Increase Decrease Attributable to undercharging Internal short circuits Possible decrease followed by an increase Decrease Internal short circuits can cause resistance to decrease. If resistance subsequently increases this may cause self-discharge, which will cause the voltage to fall. Temperature decrease Increase Decrease Low temperature degrades the cell chemical reaction, slows the chemical process, and limits available capacity. Temperature increase Decrease Increase High temperatures accelerate the cell chemical reaction, shorten the cell life, and increase the available capacity. Rated cell capacity Decrease Increase Resistance tends to decrease as cell size increases.A number of factors affect the internal resistance and capacity of a cell simultaneously. However, not all factors affect a cells capacity to the same degree as they affect internal resistance and vice-versa. In this project, both internal resistance measurements and capacity tests were taken on a periodic basis. The measurements were then compared in order to determine the relationship between capacity and internal resistance measurements.
Method description
DV Power has developed several models of battery load banks used for capacity testing, as well as a device for internal resistance testing. These units were used all over the world in cooperation with our customers and results were obtained in order to evaluate the relationship between internal resistance measurements and battery capacity, as well as to check the viability of using internal resistance as an indicator of cell and battery capacity. Batteries in this paper are used in electric utility applications. Some interesting examples are shown in the table 2.
Table 2 Battery Types Battery Type Nominal capacity Discharge current C – rate Internal resistance VRLA – TPL – 12V 100 AH 85 Ah 28,7 A C3 Approx. 3.70 mΩ Pure Lead – NSB 60FT HT RED 51/52 Ah 17 A C3 4.3 mΩ @ 25°C (77°F) VRLA (AGM) – CT200-12 149 Ah 49 A C3 Approx. 3.0 mΩThe first step was to perform an internal resistance test in order to check for suspicious results and increased resistances in the battery string. After that the capacity test was performed and the results were compared.
The following test equipment was used to measure the internal resistance and capacity of stationary battery cells:
saimr contains other products and information you need, so please check it out.
Internal resistance measurements were taken before a battery capacity test. During the capacity test voltage of each cell was measured and capacity was calculated upon completion of the test. Then internal resistance measurements were compared to the individual cell capacities to determine the trend performance. For older batteries that are ready to be replaced or should be replaced, internal resistance measurements can identify low capacity cells in a battery string, however resistance data cannot always be directly correlated to a capacity test, because there are many variables at work during a discharge that may influence the test results.
It is possible that a battery with internal resistance reading which is high in comparison to others in a string will maintain an acceptable voltage longer during a discharge than other batteries in the string with comparatively lower resistance readings. Figures below show some test results of a batteries where the capacity and internal resistance do not match.
In Figure 1 we can see that cells 5, 7 and 14 had higher resistances like cells 7 and 2, however its voltage was within the limits at the end of the capacity test.
On the graphs shown in the Figure 2 we can see the match between internal resistance and capacity results. Cell 1 and 8 high internal resistance results. That degradation was confirmed after capacity testing.
In Figure 3 it can also be seen that we do not have perfect match. After internal resistance measurement the condition of the cell 5 was considered as acceptable, however after the capacity testing the cell voltage dropped.
All of the above graphs show that the internal resistance test and the capacity test will not always have the same conclusion.
This can be caused by any of the following factors:
C – Capacity at a specific temperature recommended by the manufacturer.
Ta – Actual time duration of the test until reaching the specified string end voltage
Tm – Manufacturer’s rated time to reach the string end voltage
Kt – Temperature correction factor as per the IEEE standard
Conclusion
According to experience, internal resistance measurements can detect deterioration of a battery. However, internal resistance measurements cannot tell everything regarding the battery capability or condition.
Some points to consider are:
From the above considerations it is clear that each test has its merits, but on balance a capacity test is a more accurate way to determine where the battery is on its predictable life curve.